The 4-20 mA output signal of the RPI sensors, which is supplied by the two-wire transmitter, can be processed in all common industrial control systems and does not need to be calibrated when the sensor is connected. The output signal for pressure and temperature measurement of the RPI+T sensors is a 0-10 V signal each and can be processed in all common industrial controls. When the sensor is connected, it does not need to be calibrated.
The sensor RPI requires a power supply of 12.5-30 VDC.
The sensor RPI+T requires a power supply of 16.6-30 VDC.
RPS (0.5-3.5 V / 5 VDC)
The output signal for pressure and temperature measurement of the RPS sensors is a 0.5-3.5 V ratiometric signal for pressure measurement and a 0.5-4.1 V ratiometric signal for temperature measurement and can be processed in all common industrial control systems. When connecting the sensor it does not need to be calibrated.
The RPS sensor requires a power supply of 5 VDC ± 5 %.
RPS7 (4-20mA / 12-30 VDC)
The 4-20 mA output signal of the RPS7 sensors, which is supplied by the two-wire transmitter, can be processed in all common industrial control systems and does not need to be calibrated when the sensor is connected.
The sensor RPS7 requires a power supply of 12-30 VDC.
RPS8 (0.5-3.5 V / 12-30 VDC)
The output signal for pressure and temperature measurement of the RPS8 sensors is a 0.5-3.5 V ratiometric signal for pressure measurement and a 0.5-4.1 V ratiometric signal for temperature measurement and can be processed in all common industrial control systems. When connecting the sensor it does not need to be calibrated.
The RPS8 sensor requires a power supply of 12-30 VDC.